Once a dry-type transformer is put into operation it enters the working state and becomes live, so great care must be taken to avoid the danger of electric shock. In actual energizing operation, the following points should be noted:
In short, safety comes first in every energizing operation of a dry-type transformer — any improper operation that could cause an accident must be eliminated.
A distribution transformer is a type of transformer dedicated to supplying power around large transformers. Large transformers usually need more electricity to operate, so distribution transformers are often installed around them. A distribution transformer is different from a transformer's distribution switchgear: the switchgear only transmits electric energy, whereas a distribution transformer transmits both electric energy and voltage.
Fuses should be installed on both the high- and low-voltage sides. The bottom of the high-voltage fuse must be at least 4.5 m above ground, with a horizontal phase spacing of at least 0.5 m; so that the fuse tube can fall smoothly after the fuse melts, the axis of the drop-out fuse should form a 15%–30% angle with the vertical. The bottom of the low-voltage fuse must be at least 3.5 m above ground with a phase spacing of at least 0.2 m.
Drop-out fuse links are selected on the principle that they must melt quickly when a short circuit occurs inside the transformer or on its high/low-voltage outgoing lines; the fusing time must be ≤ 0.1 s. For capacities below 100kVA, the high-voltage fuse rating is selected at 2–3 times the transformer rated current; above 100kVA, at 1.5–2 times. The low-voltage fuse is selected according to the low-voltage rated current.
Most external threats to distribution transformer operation come from lightning. A lightning protection device should be installed, using gapless metal-oxide surge arresters with synthetic insulation housing, which offer strong power-frequency voltage withstand, good sealing and stable protection characteristics. Note that arresters mounted on the transformer with iron plates connecting them together is an incorrect practice.
Oil-immersed transformers play an active role in improving current and voltage. In production, operation and maintenance, their inspection, use and maintenance levels should be continuously improved. The main components are:
These are the common components of an oil-immersed transformer, provided for your reference.
In terms of price, a dry-type transformer is more expensive than an oil-immersed one. Inside comprehensive buildings (basements, floors, rooftops) and in crowded places, dry-type transformers must be used; oil-immersed transformers are used at independent substation sites. Dry-type units are generally used in box-type (compact) substations; oil-type is generally used for outdoor temporary power supply. Choose according to the available space — where space is large an oil-immersed unit can be used, where space is tight a dry-type unit is preferred. In humid and hot regions, oil-immersed is preferred; if a dry-type unit is used there, forced-air cooling equipment must be fitted.
A high-frequency transformer is a power transformer working at frequencies above medium frequency (10kHz). It is mainly used as the transformer in high-frequency switching power supplies, and also in high-frequency inverter power supplies and high-frequency inverter welding machines. Its main uses are reflected in the following points:
High-frequency transformers are also applied in everyday appliances such as radios, televisions and microwave ovens — especially in switching power supplies.
Oil leakage arises partly from defects hidden in the transformer design and manufacturing process, and partly from improper installation and maintenance. Leakage most often occurs at radiator interfaces, flat butterfly-valve caps, bushings, porcelain insulators, weld seams, sand holes and flanges.
Yes. In addition to the standard series shown on our Products page, Suzhou Boyuan designs and manufactures all kinds of special transformers according to customer requirements. Send us your specifications — furnace data, voltage, capacity, impedance, connection group and site conditions — through the contact form, and our engineering team will reply with a tailored proposal.